Glycol chiller won't hold setpoint — compressor short-cycling

Awaiting Spares

marcus.whelan@bantambarrel.demo · 2026-08-13 11:33:30 · ISS-QC-0015

Edit in Desk ↗
Customer
No customer linked
Machine / asset
Glycol Chiller
serial GC-2016-04 · MACH-0005
DisciplineCellar
PriorityHigh
Spares statusOrdered
Last updated2026-08-14 23:33

Description

Glycol loop temperature swings ±4°F instead of holding ±1°F, compressor short-cycling every 6–8 minutes. FV1 (Roost) and FV6 (Nesting) cooling are both riding warmer than setpoint during active fermentation. Brewhouse holding off on the next lager pitch until it's fixed.

Work log

Currently: Waiting2 entries
  1. MWmarcus.whelanWaitingAug 14 · 11:33 PM

    Replacement contactor on order. Cellar team briefed to watch FV1/FV6 temps closely in the meantime.

  2. MWmarcus.whelanDiagnosedAug 13 · 01:33 PM

    Compressor contactor is chattering under load — points at the contactor, not the refrigerant charge.